MPS Microgrid Series – Industrial Energy Solution (Power Cabinet)
An integrated power cabinet solution designed for photovoltaic (solar) and wind energy storage, suitable for industrial and commercial applications, as well as remote areas without access to the power grid. This all-in-one system combines energy storage and power management components into a compact, ready-to-deploy unit, making it ideal for a wide range of off-grid and hybrid energy setups.



Product Features
- All-in-one integrated design
- Compact, high power density
- Automatic peak/valley charging
- BMS & EMS coordination
- Multi-level system protection
- Up to 90% system efficiency
| Off-Grid Operation | |
| AC Start-up / Auto Restart Voltage | 120–140 VAC / 180 VAC (both) |
| Acceptable Input Voltage Range | 170–290 VAC per phase (both) |
| Maximum AC Input Current | 40A (both) |
| PV Input Max. DC Power | 30KW | 45KW |
| Max. DC Voltage | 950 VDC (both) |
| MPP Voltage Range (Off-Grid) | 550 ~ 900 VDC (both) |
| MPPT Trackers / Max. Input Current | 1 / 48A | 1 / 72A |
| General / Interface / Environment | |
| Communication Port | RS-232/USB |
| Intelligent Slot | Optional SNMP, GPRS, WIFI, Modbus cards available |
| Humidity | 0 ~ 90% RH (non-condensing) |
| Operating Temperature | -10°C to 60°C |
| Altitude | 0 ~ 1000 m |
Specification
| Models | HV 20KW Inverter+40KWh Battery | HV 30KW Inverter+61KWh Battery |
| Maximum PV Input Power | 30KW | 45KW |
| Rated Output Power | 20KW | 30KW |
| Grid-Tie Operation | |
| Nominal / Maximum DC Voltage | 720 VDC / 950 VDC (both models) |
| Start-up / Initial Feeding Voltage | 500 VDC / 550 VDC (both) |
| MPP Voltage Range | 460 ~ 900 VDC (both) |
| Full Power MPP Voltage Range | 625 ~ 900 VDC (both) |
| MPPT Trackers / Max. Input Current | 1 / 48A | 1 / 72A |
| Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) (both) |
| Output Voltage Range | 184–265 VAC per phase | 195.5–253 VAC per phase |
| Output Frequency Range | 49~51Hz or 59.3~60.5Hz (both) |
| Nominal Output Current | 29.0A per phase | 43.5A per phase |
| Power Factor Range | >0.99 | 1 |
| Max. Conversion Efficiency (DC/AC) | 91% | 95% |
| Hybrid Operation | |
| Maximum DC Voltage | 720 VDC (both) |
| Start-up / Initial Feeding Voltage | 500 VDC / 550 VDC (both) |
| MPP Voltage Range | 550 ~ 900 VDC | 460 ~ 900 VDC |
| MPPT Trackers / Max. Input Current | 1 / 48A | 1 / 72A |
| Nominal Output Voltage | 230 VAC (P-N) / 400 VAC (P-P) (both) |
| Output Voltage Range | 184–265 VAC per phase | 195.5–253 VAC per phase |
| Output Frequency Range | 47.5~51.5Hz or 59.3~60.5Hz (both) |
| Nominal Output Current | 29A per phase | 43.5A per phase |
| Power Factor | >0.99 | 1 |
| AC Start-up / Auto Restart Voltage | 120–140 VAC/180 VAC per phase | 150–170 VAC/180 VAC per phase |
| Acceptable Input Voltage Range | 170–280 VAC per phase (both) |
| Maximum AC Input Current | 40A per phase | 43.5A per phase |
| Battery Nominal Voltage | 409.6 VDC (both) |
| Nominal Battery Capacity | 100Ah | 150Ah |